National Instruments FP-AO-V10B Analog voltage output module
1 image: Click to enlarge
National Instruments · FieldPoint

FP-AO-V10B

The FP-AO-V10B provides two single-ended ±10 V analog outputs with 12-bit resolution.

ManufacturerNational Instruments
ModelFP-AO-V10B
Product TypeAnalog voltage output module
● Available to Order
Condition: confirmed per unit

Request current pricing and lead time for this model. Our team will confirm the exact equipment configuration and condition.

Fast RFQ

Quote: FP-AO-V10B

We will reply by email.
Free Shippingfull policy linked
30-Day Warrantystandard coverage
30-Day Returnspolicy applies
Technical Supportmodel & compatibility help
Channels2
Range±10 V
Resolution12 bits
SOHO Assistant
Ask about this exact model, a replacement, accessory, driver, rental or repair question.
Ask about specifications, compatibility, availability, rental or repair.
Ask SOHO Assistant
Overview

Product overview

Key product information and technical features.

This dual-channel FieldPoint module mounts on the FP-TB-10 terminal base.

  • Bipolar voltage outputs.
  • 10 mA drive per channel.
  • Shared channel reference.
Verified specifications

Technical data

Verified product specifications.

Outputs2 single-ended
Output range−10 to +10 V
Resolution12 bits
Voltage increment4.9 mV
Output impedance10 Ω
Output drive per channel10 mA
Condition & included items

What the actual unit includes

Confirm condition, included accessories and revision before ordering.

Condition

Confirmed per unit.

Included

Device / accessories confirmed in quote.

Revision

Exact revision confirmed when relevant.

Compatibility

Complete the measurement chain

Review system components and compatibility requirements.

National Instruments

Manufacturer

FieldPoint

Distributed I/O platform

FP-TB-10

Terminal base

Compatibility

Designed for the FP-TB-10 terminal base.

Channels share a reference; they are not individually isolated.
Manuals & software

Technical resources

Manuals, software and technical resources for this model.

Shipping, warranty & returns

Commercial terms

Review shipping, warranty and return terms before ordering.

Shipping
Free Shipping. Full policy terms apply.
Warranty
30-Day Warranty. Standard coverage applies.
Returns
30-Day Returns. Return policy applies.
Price / Availability
Contact SOHO ProLab for current quote and availability.
Lifecycle services

Source, rent or repair the exact model

Choose pricing, rental or repair for this exact model.

Related products

Alternatives & system components

Explore equipment

FieldPoint -- Modular Distributed I/O

Shipping, warranty and returns

FAQ

Product-specific questions

Product-specific answers based on available technical information.

How does it differ from FP-AO-V10?

FP-AO-V10B outputs ±10 V; FP-AO-V10 outputs 0–10 V.

Does loading affect output voltage?

Yes. The 10 Ω output impedance adds 10 mV error per milliampere supplied.

Ask SOHO AssistantProduct & compatibility help